Discussion of solution of several questions of design in the power transformer protection QUAN Xian-jun, WAN Xiang-yang, LIU Shi-ming, LI Xiao-bin,DENG Xiang-li (Yantai Dongfang Electronics Information Industtry Co.,Ltd,Yantai 264000,China) Abstract: The several technology questions of the design about high voltage and ultra-high voltage large power transformer protection is introduced.The paper describes the solution and discussion about them in detail. Adopt zero sequence current compensation to revise the currents is avail for identifying magnetizing inrush current and improve sensitivity of the earth-fault;The fault member differential relay improve sensitivity of the interturn fault and high resistance earth-fault about light faults;The problem of influence of CT saturation to differential relay is solved by area of characteristic of additional stabilization; Adopt integrate distinguish of current and voltage identify the break or short of secondary circuit of CT; Adopt setting N group sets to imitate curve of overexcitation solve the problem of adapt for engineering. Key words: magnetizing inrush current; zero sequence current compensation; fault member; break or short; overexcitation (